Air-cooled screw chillers are widely used in industrial refrigeration projects of different scales in various industries, such as factory equipment cooling and chemical industry, printing presses, planting, reactors, fermentation tanks, hospitals, refrigeration, and refrigeration. KDCS screw chillers are our company The experience of designing and producing water chillers, combined with the latest technological development, has concentrated on research, design, and development of chillers. The product keeps up with the development trend of the times, adhering to the design concept of “high efficiency, reliability, energy saving, and environmental protection” to provide users with excellent refrigeration equipment.

Description

Air-cooled screw chillers are widely used in industrial refrigeration projects of different scales in various industries, such as factory equipment cooling and chemical industry, printing presses, planting, reactors, fermentation tanks, hospitals, refrigeration and refrigeration. KDCS screw chillers are our company The experience of designing and producing water chillers, combined with the latest technological development, has concentrated on research, design and development of chillers. The product keeps up with the development trend of the times, adhering to the design concept of “high efficiency, reliability, energy saving, and environmental protection” to provide users with excellent refrigeration equipment.

Specification

ModelKDCS-120DLA
Power Supply Voltage3Φ-50Hz-380V
Cooling Capacity104 ton (366 kw, 314,760 kcal/h)
Compressor TypeSemi-Hermetic screw type
Compressor Power107.5 kw
Refrigerant TypeR22 (R134a, R407c, R404a, R507c Optional)
Refrigerant Control modeThermostatic expansion valve
Refrigerant Filling Amount58 kg
EvaporatorShell and tube type
CondenserFinned type
Cooling Fan TypeLow noise outer rotor fan
Cooling Fan Air volume1790 cmm
Cooling Fan Power2.2*6 kw
Input Power116.3 kw
Chilled Fluid Flow60 m3/h
DimensionL*W*H=4400*2100*2100mm
Weight3420 kg
NoteTechnical specifications based on 12°C/7℃ Inlet/outlet chilled fluid temperature. Outdoor ambient temperature DB35℃/WB24℃. Data is subject to change without notice.